TRICHY RESIDENCY 3.29 kW

LEAD DESIGNER

Jacob Wood, design and sales manager, True South Solar, truesouthsolar.net

LEAD INSTALLER

Eric Hansen, general manager, True South Solar

DATE COMMISSIONED

August 2013

LOCATION

Jacksonville, OR, 42°N, 122°W

SOLAR RESOURCE

4.5 kWh/m2/day

ASHRAE EXTREME MIN/0.4%HIGH TEMPERATURE

–8°C/40°C

ARRAY CAPACITY

3.29 kW DC@STC, ANNUAL AC PRODUCTION: 3,822kWh

MODULES
  • 14) Sharp NU235 F2, 235Watts STC
  • -5%/+10%, 7.84 Imp
  • 30 Vmp, 8.60 Isc, 37Voc
INVERTER
  • (1) Fronius IG Plus 3.0, 3000 Watts
  • 600 Vdc maximum input
  • 230-500 Vdc MPPT range, 240V Single Phase AC output.
ARRAY
  • (14) modules per source circuit. (STC Rating per string Watts: 3,290, Imp: 7.84A,
  • Adjusted Voc (low temp): 578V Isc: 8.60, Typical Operating Vmp: 420V.
  • (1) Source circuits per inverter.
ARRAY INSTALLATION

Racking: Snap N Rack engineered and flashed flush mount to composite shingle roofing, 115° azimuth, 26° tilt.